Troubleshooting and Repair Instructions
The troubleshooting and repair instructions are only
applicable to the following unit versions
AIRTRONIC L engine-independent air heater
for petrol engines
Heater Order No.
AIRTRONIC
L – B5, 12 volt 20 1859 05 00 00
AIRTRONIC L engine-independent air heater
for diesel engines
Heater Order No.
AIRTRONIC L – B5, 12 volt 25 2361 05 00 00
AIRTRONIC L – D5, 24 volt 25 2362 05 00 00
Vue de la page 0
1 2 3 4 5 6 ... 53 54

Résumé du contenu

Page 1

EberspächerJ. EberspächerGmbH & Co. KGEberspächerstr. 24D-73730 EsslingenPhone (switchboard)(0711) 939-00Fax(0711) 939-0500www.eberspaecher.comL25

Page 2 - List of Contents

10What to check first in case of faults• Check– Fuel in the tank?– Fuel pipes leaking? (visual check)– Summer diesel in the fuel pipe?– Combustion air

Page 3

11Troubleshooting4Overview of the individual test equipmentand control unitsThe electronic control box can store up to 5 errors, which canbe read out

Page 4 - Introduction

12Troubleshooting4Caution!Operating voltage safety information!Ensure you use the correct operating voltage, otherwise theconnected components can be

Page 5 - Function

13Display of the fault memory F1 – F5 or F5 – F1• The heater is switched on.• Press the buttons e and f once or several times todisplay the individual

Page 6

14Troubleshooting4Cancel the control box lock• Delete the fault memory as described and switch off theheater using the d button.• The control box lock

Page 7

15Troubleshooting4EDiTH customer service programwith ISO adapterOrder No. 22 1524 89 00 00An additional adapter cable is required to connect the ISOad

Page 8 - Product information

16Troubleshooting4Caution!Magnetic field!During the test operation a magnetic field develops at theadapter. Therefore, do not place any objects such a

Page 9

17Troubleshooting4Module timer(Order No.: 22 1000 30 34 00)The current fault is displayed as “AF” and is always written inmemory position F1.Preceding

Page 10 - Troubleshooting

18Fault diagnosis using the radio remotecontrol TP5TP5 radio remote controlOrder No. 22 1000 32 01 00If faults occur while the heater is running, they

Page 11

194The following actions are possible• Call up fault memory.Call up the fault memory positions F1 – F5 with or .• Call up fault memory

Page 12

24311IntroductionThis list of contents gives you precise information about thecontents of the Troubleshooting and Repair Instructions.If you are looki

Page 13

Fault code Fault description CommentsDisplay • Remedial actionTroubleshooting20––• Disconnect connector S1 / B1 at the heater and at the connector B1,

Page 14

Fault code Fault description CommentsDisplay • Remedial actionTroubleshooting214015017020021022025030031Operating lock-outOverheatingGlow plug – inter

Page 15

Fault code Fault description CommentsDisplay • Remedial actionTroubleshooting224032034047048049050051052053054055056Blower motor – earth short circuit

Page 16

Fault code Fault description CommentsDisplay • Remedial actionTroubleshooting23• Disconnect the plug-in connection of the external room temperature se

Page 17

Fault code Fault description CommentsDisplay • Remedial actionTroubleshooting24Control box defective(internal fault)Control box defective(ROM error)Co

Page 18

25Repair instructions5Repair instructionsThe permitted repair work to the heater is described in the„Repair Instructions“ chapter. If extensive repair

Page 19

26Repair instructions5Assembly drawing

Page 20

27Repair instructions5Parts list1 Heat exchanger, complete with combustion chamber2 Combustion chamber cover3 Seal combustion chamber4 Combustion air

Page 21

28Repair instructions5햴햳햵햶햲햲햲햲Repair step 1Dismantle / assemble glow plug(Figure 1)• Remove large angular rubber grommet.• Unscrew M4 fixing nut of th

Page 22

29Repair instructions5햲b햲햲햳햲햲햳Repair step 4Dismantle / assembly combination sensor(overheating / flame sensor)(Figure 4 – 6)• Repair step 3, dismantle

Page 23

381IntroductionRepair instructionsCircuit diagramServiceIndex57Chapter Title Contents PageList of Contents6• Repair instructions...

Page 24

30Repair instructions5Table of overheating sensor valuesTemperature °C Resistance kΩ min. max.–40 1597.00 1913.00–20 458.80 533.400 154.70 175.5020 59

Page 25 - Repair instructions

31Repair instructions5햲햲햲햲햲햳햲햲햲햲Repair step 5Dismantle / assemble combustion air fan(Figure 7 – 11)• Repair step 3, dismantle / assemble control box.•

Page 26

32Repair instructions5Repair step 6Replace the combustion chamber cover seal(Figure 12)• Repair step 5, dismantle / assemble combustion air fan.• Unsc

Page 27

33Repair instructions5Check fuel supplyBefore measuring the fuel quantity, check the following points inthe fuel supply.• Check the screen in the mete

Page 28

34Circuit diagram6Parts list circuit diagrams AIRTRONIC L /AIRTRONIC L – ADR1.1 Burner motor1.2 Glow plug1.5 Overheating and flame sensor2.1 Control b

Page 29

35Circuit diagram6Parts list page 34 25 2361 00 98 01 AAIRTRONIC L circuit diagram – 12 volt / 24 volt

Page 30

36Circuit diagram6Parts list page 34Circuit diagram for control units25 2069 00 97 01 C25 2069 00 97 03 B

Page 31

37Circuit diagram6Parts list page 34Circuit diagram for control units25 2069 00 97 02 A

Page 32

38Circuit diagram6Parts list page 34Circuit diagram for control units25 2069 00 97 02 A

Page 33

39Circuit diagram6Parts list page 34Circuit diagram for control units25 2069 00 97 04 A

Page 34 - Circuit diagram

4Introduction1These Troubleshooting and Repair Instructions are applicableto the heaters listed on the title page, to the exclusion of allliability cl

Page 35

40Circuit diagram6Parts list page 34Circuit diagram for control units25 2069 00 97 04 A

Page 36

41Parts list page 34Circuit diagram6Circuit diagram AIRTRONIC L – ADR – 12 volt / 24 volt25 2361 00 96 01 A

Page 37

42Circuit diagram6Circuit diagram control units – ADR25 2069 00 96 01 BParts list page 34

Page 38

43Circuit diagram6Parts list circuit diagram control unitEasyStart R+ / R / T2.15.1 Temperature sensor (room temperature)(included in scope of supply

Page 39

44Circuit diagram61 Terminal 31 (negative)2 – –3 Ventilate (switching signal –)4 DAT cable5 Pushbutton / LED (negative)6 Temperature sensor (negative)

Page 40

45Circuit diagram6Circuit diagram control units – EasyStart R+This circuit diagram is for heaters with 2 diagnostics cableand whose control box cable

Page 41

46Circuit diagram6Circuit diagram control units – EasyStart R25 2361 00 97 05 BParts list page 43

Page 42

47Circuit diagram6Circuit diagram control units – EasyStart R25 2361 00 97 02 BThis circuit diagram applies to control boxes with twodiagnostic cables

Page 43

48Circuit diagram6This circuit diagram is for heaters with 2 diagnostics cable andwhose control box cable loom is wound with cable tape.25 2361 00 97

Page 44

49Circuit diagram6Circuit diagram control units – EasyStart T – ADRThis circuit diagram is for heaters with 2 diagnostics cable andwhose control box c

Page 45

5Function2Cutaway view1 Module timer2 Changeover switch „heat / ventilate“3 Fuse bracket– Main fuse 25 A– Fuse, „actuation“ 15 A4 Heater impeller5 Con

Page 46

50Service7CertificationsThe high quality of Eberspächer’s products is the key to oursuccess.To guarantee this quality, we have organised all workproce

Page 47

51Service7Representatives abroadArgentinaAGCO Argentinia S. A.Valentin Gomez 5771706 HaedoRA - Pcia. Buenos AiresTel. 0054 / 1 - 483 32 01Fax. 0054 /

Page 48

52Service7Representatives abroadSwedenSvenska Eberspächer ABBox 2103S - 12823 SkarpnäckTel. 0046 / 86 83 11 00Fax. 0046 / 87 24 90 40SwitzerlandTechn

Page 49

53Index8IndexKeyword Page Keyword PageAAccident prevention ... 4Adapter cable ...

Page 50 - EC Declaration of Conformity

54Index8List of abbreviationsADREuropean agreement about the international transport ofdangerous goods on the road.EC type-approvalPermit awarded by t

Page 51 - Representatives abroad

6Function2Description of functionsSwitching on / starting the heaterWhen the heater is switched on, the control lamp in thecontrol unit lights up.The

Page 52

7Function2Please note!Control and safety devices• If the heater does not ignite within 90 seconds after the fuelstarts to pump, the start is repeated.

Page 53

8AIRTRONIC L – B5 AIRTRONIC L – D5Air AirStage StagePower High Medium Low Power High Medium Low5500 4800 2700 1200 5500 4800 2700 1500280 275 180 125

Page 54 - List of abbreviations

9Test speed for the blowerHeater 12 voltAt 11.3 volt n = 4650 – 7000 U/minHeater 24 voltAt 23.6 volt n = 4650 – 6500 U/minResistance values 12 V 24